Description of device parameters
Proline Promag 300 Modbus RS485
108
Hauser
0/4 mA value
Navigation
Expert → Output → Curr.output 1 to n → 0/4 mA value (0367–1 to n)
Prerequisite
One of the following options is selected in the
Current span
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Description
Use this function to enter a value for the 0/4 mA current.
User entry
Signed floating-point number
Factory setting
Country-specific:
• 0 l/h
• 0 gal/min (us)
Additional information
Description
Positive and negative values are permitted depending on the process variable assigned in
the
Assign curr.
parameter (→ 106). In addition, the value can be greater than or
smaller than the value assigned for the 20 mA current in the
20 mA value
parameter
Dependency
The unit depends on the process variable selected in the
Assign curr.
parameter
Current output behavior
The current output behaves differently depending on the settings configured in the
following parameters:
• Failure mode (→ 116)
Configuration examples
Some examples of parameter settings and their effect on the current output are given in
the following section.
Configuration example A
Measuring mode with
Forward flow
option
•
0/4 mA value
parameter (→ 108) = not equal to zero flow (e.g. –250 m
3
/h)
•
20 mA value
parameter (→ 109) = not equal to zero flow (e.g. +750 m
3
/h)
• Calculated current value = 8 mA at zero flow
-250
20
+750
I [mA]
Q
1
1
4
0
8
A0013757
Q
Flow
I
Current
1
Measuring range is exceeded or undershot