Commissioning
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
90
Hauser
•
740:
Calculation Overflow, bad configuration
To change the assigned status (Bad, Uncertain, Good) of an event, select the desired status
from the associated picklist.
Example
The status of error 115 "Sensor overpressure" should no longer be indicated as "Uncertain"
and should instead be indicated as "Bad".
1. In the FieldCare navigation window navigate to
Expert
Field Device Diagnostics
PV Status Config
2. All the bits of the Status Select Events have the status "Uncertain" in the factory setting.
3. Select the "Bad" option for the "Status Select Event 115" row. Press Enter to confirm your
entry.