Commissioning
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
86
Hauser
2. Select the "Configurable area" tab. In the factory setting, all the bits in the
Configurable
Area Bits
column have the value
not assigned
(A).
3. Select one of these bits (here
Configurable Area Bit 15
, for instance) and select the
Sensor overpressure
(B) option from the associated picklist. Confirm your choice by
pressing "Accept".
4. Enable the check box for the bit concerned (here:
Configurable Area Bit 15
) (C).
Confirm your choice by pressing "Accept".
Additional information:
The "Status 1" and "Status 2" tabs indicate whether an event is active.
Changing the error category for
Sensor overpressure
does not affect an error that already
exists. The new category is only assigned if this error occurs again after the change has been
made. The "Status 1" and "Status 2" tabs indicate whether an event is active.