Commissioning
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
64
Hauser
6. Enter the alarm and critical alarm messages by means of the HI_HI_LIM, HI_LIM,
LO_LIM and LO_LO_LIM parameters. The limit values entered have to be within the
value range specified for the OUT_SCALE parameter.
7. Specify the alarm priorities by means of the HI_HI_PRI, HI_PRI, LO_LO_PRI and LO_PRI
parameters. Reporting to the field host system only takes place with alarms with a
priority greater than 2.
8. Set the block mode to Auto using the MODE_BLK parameter, TARGET element. For this
purpose, the Resource Block must also be set to the "Auto" block mode.
Additional configuration
1. Depending on the control or automation task, configure additional function blocks and
output blocks.
See also Operating Instructions BA00303P "Description of Device
Functions Cerabar S/Deltabar S/Deltapilot S".
2. Link the function blocks and output blocks.
3. After specifying the active LAS, download all the data and parameters to the field
device.
7.4
Selecting the language and measuring mode
7.4.1
Local operation
The MEASURING MODE parameter is on the 1st selection level.
"Menu structure".
The following measuring modes are available:
• Pressure
• Level
• Flow
7.4.2
Selecting the language and measuring mode by means of the
FieldCare operating program
Selecting the measuring mode
The parameters for setting the measuring mode are displayed in the FieldCare "Measuring
mode" menu:
Betriebsart-de
Fig. 35:
"Measuring mode" menu