Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Commissioning
Hauser
65
The following measuring mode settings are available:
Selecting the language
Select the menu language for FieldCare using the "Language Button" in the configuration
window. Select the menu language for the FieldCare frame by means of the "Extra" menu
"Options" "Display"
"Language".
The following languages are available:
• Deutsch
• English
• Français
• Español
• Chinese
• Japanese
7.5
Position adjustment
Due to the orientation of the device, there may be a shift in the measured value, i.e. when
the container is empty or partly filled, the measured value parameter does not display zero.
There are three options to choose from when performing position adjustment.
• Onsite display menu path: GROUP SELECTION
OPERATING MENU
SETTINGS
POSITION ADJUSTMENT
• FieldCare menu path: OPERATING MENU
SETTINGS
POSITION ADJUSTMENT
7.5.1
Performing position adjustment via the onsite display or
FieldCare
The parameters listed in the following table can be found in the POSITION ADJUSTMENT
group (menu path: OPERATING MENU
SETTINGS
POSITION ADJUSTMENT).
Primary Value Type
Linearization
Level selection
Pressure
None
-
Flow
Root function
-
Level, mass, volume
None
Level Easy Pressure
Level, mass, volume
None
Level Easy Height
Level, mass, volume, tank content in %
None
Level Standard
Level, mass, volume, tank content in %
Level linearized
Level Standard
Level, mass, volume, tank content in %
Level combined
Level Standard
Parameter name
Description
POS. ZERO ADJUST
Entry
Position adjustment – the pressure difference between zero (set point) and the
measured pressure need not be known.
Example:
– MEASURED VALUE = 2.2 mbar (0.032 psi)
– Correct the MEASURED VALUE via the POS. ZERO ADJUST parameter with the
"Confirm" option. This means that you are assigning the value 0.0 to the pressure
present.
– MEASURED VALUE (after pos. zero adjust) = 0.0 mbar
The CALIB. OFFSET parameter displays the resulting pressure difference (offset) by
which the MEASURED VALUE was corrected.
Factory setting:
0.0