Diagnostics and troubleshooting
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
106
Hauser
9.5.4
Out of specification (S)
Diagnostic
Code
Error
response
Message/description XD_
ERROR
Value Bit
BLOCK_
ERROR
Value Bit
Cause
Measure
Prio-
rity
115 Alarm/
warning
S>Sensor overpressure 17
0
– Overpressure present.
– Reduce pressure until
message disappears.
31
– Sensor defect.
– Replace sensor.
120 Alarm/
warning
S>Sensor low pressure 17
0
– Pressure too low.
– Increase pressure until
message disappears.
32
– Sensor defect.
– Replace sensor.
715 Alarm/
warning
S>Sensor over
temperature
17
7
– The temperature measured in
the sensor is greater than the
upper nominal temperature
of the sensor. (
See also
Operating Instructions
BA00303P, parameter
description for
TEMPERATURE_1
_SENSOR_LIMIT_HIGH/
Tmax SENSOR or these
Operating Instructions)
– Reduce process temperature/
ambient temperature.
34
– Unsuitable download carried
out.
– Check configuration and
perform download again.
717 Alarm/
warning
S>Transmitter
over temperature
17
0
– The temperature measured in
the electronics is greater than
the upper nominal
temperature of the electronics
(+88 °C (+190 °F)).
– Reduce ambient temperature. 36
– Unsuitable download carried
out.
– Check configuration and
perform download again.
718 Alarm/
warning
S>Transmitter
under temperature
17
0
– The temperature measured in
the electronics is smaller than
the lower nominal
temperature of the electronics
(–43 °C (-45 °F)).
– Increase ambient
temperature. Insulate device
if necessary.
37
– Unsuitable download carried
out.
– Check configuration and
perform download again.
720 Alarm/
warning
S>Sensor
under temperature
17
0
– The temperature measured in
the sensor is lower than the
lower nominal temperature of
the sensor (
see Operating
Instructions BA00303P,
parameter description,
TEMPERATURE_1
_SENSOR_LIMIT_LOW/
Tmin SENSOR parameter).
– Increase process
temperature/ambient
temperature.
35
– Unsuitable download carried
out.
– Check configuration and
perform download again.
– Loose connection at sensor
cable.
– Wait a short period of time
and tighten the connection, or
avoid loose connection.