Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Diagnostics and troubleshooting
Hauser
109
The value specified by means of the FSAFE_VALUE
1
parameter is used for further
processing with the status UNCERTAIN.
• Wrong Value
The current value is used for further processing with the status BAD.
Factory setting:
• FSAFE_TYPE: FsafeValue
• FSAFE_VALUE: 0
The failsafe mode is also activated if the "Out of service" option was selected by means of the
MODE_BLK parameter, "Target" element.
9.7
Confirming messages
Depending on the settings for the ALARM_HOLD_ON_TIME/ALARM DISPL. TIME and
ACKNOWLEDGE_ALARM_MODE/ACK. ALARM MODE parameters, the following
measures should be taken to clear a message:
9.8
Repair
The Hauser repair concept provides for measuring devices to have a modular design
and also that the customer may carry out repairs
110 "Spare Parts" on ).
• For certified devices, please consult the "Repair of Ex-certified devices" section.
• For more information on service and spare parts contact the Hauser Service.
(
See www.endress.com/worldwide.)
1 These parameters are not available by means of the FieldCare operating program.
Settings
1)
1)
FF configuration program: The parameters are in the Diagnostic Transducer Blocks.
FieldCare: Menu path for ALARM DISPL. TIME and ACK. ALARM MODE: OPERATING MENU
DIAGNOSTICS
MESSAGES
Measures
– ALARM_HOLD_ON_TIME/
ALARM DISPLAY TIME = 0 s
– ACKNOWLEDGE_ALARM_MODE
/ACK. ALARM MODE = off
– Rectify the cause of the message (see also Section 9.5).
– ALARM_HOLD_ON_TIME/
ALARM DISPL. TIME > n s
– ACKNOWLEDGE_ALARM_MODE
/ACK. ALARM MODE = off
– Rectify the cause of the message (see also Section 9.5).
– Wait for the alarm display time to elapse.
– ALARM_HOLD_ON_TIME/
ALARM DISPL. TIME = 0 s
– ACKNOWLEDGE_ALARM_MODE
/ACK. ALARM MODE = on
– Rectify the cause of the message (see also Section 9.5).
– Confirm message using ACKNOWLEDGE_ALARM/ACK. ALARM
parameter.
– ALARM_HOLD_ON_TIME/
ALARM DISPL. TIME > n s
– ACKNOWLEDGE_ALARM_MODE
/ACK. ALARM MODE = on
– Rectify the cause of the message (see also Section 9.5).
– Confirm message using ACKNOWLEDGE_ALARM/ACK. ALARM
parameter.
– Wait for the alarm display time to elapse. If a message appears and the
alarm display time elapses before the message has been acknowledged,
the message is cleared once it has been acknowledged.
Содержание Deltabar S FMD77