Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
6
Hauser
1.4
Terms and abbreviations
A0029505
Position Term/Abbreviation
Explanation
1
OPL
The OPL (over pressure limit = sensor overload limit) for the sensors
depends on the lowest-rated element, with regard to pressure, of the
selected components, i.e. the process connection must be taken into
consideration in addition to the measuring cell. Also observe pressure-
temperature dependency. For the relevant standards and additional notes,
see technical information.
The OPL may be applied for a limited time period.
2
MWP
The MWP (maximum working pressure) for the sensors depends on the
lowest-rated element, with regard to pressure, of the selected components,
i.e. the process connection has to be taken into consideration in addition to
the measuring cell. Also observe pressure-temperature dependency. For the
relevant standards and additional notes, see technical information.
The MWP may be applied for an unlimited time.
3
Maximum sensor
measuring range
Range between LRL and URL
This span is the maximum calibratable/adjustable measuring span.
4
Calibrated/Adjusted
measuring span
Range between LRV and URV
Factory setting: 0...URL
Other calibrated spans can be ordered with customised settings.
p
-
Pressure
-
LRL
Lower range limit
-
URL
Upper range limit
-
LRV
Lower range value
-
URV
Upper range value
-
TD
Turn down
URL
OPL
MWP
LRL
0
p
LRV
URV
1
2
3
4