Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Diagnostics and troubleshooting
Hauser
107
726 Alarm/
warning
S>Sensor temperature
error - overrange
20
7
– Electromagnetic effects are
greater than specifications in
the technical data.
(
– Block off electromagnetic
effects or eliminate source of
disturbance.
33
– Process temperature is
outside permitted range.
– Check temperature present,
reduce or increase if
necessary.
– Sensor defect.
– If the process temperature is
within the permitted range,
replace sensor.
727 Alarm/
warning
S>Sensor pressure
error - overrange
20
7
– Electromagnetic effects are
greater than specifications in
the technical data.
(
See Section 10.)
– Block off electromagnetic
effects or eliminate source of
disturbance.
30
– Pressure is outside permitted
range.
– Check pressure present,
reduce or increase if
necessary.
– Sensor defect.
– If the pressure is within the
permitted range, replace
sensor.
730 Alarm/
Warning
S>Pmin ALARM
WINDOW
(PRESSURE_1_USER_
LOW_LIMIT)
undershot
19
0
– Pressure measured value has
undershot the value specified
for the PRESSURE_1_USER_
LOW_LIMIT/Pmin ALARM
WINDOW parameter.
– Check system/pressure
measured value.
– Change value for
PRESSURE_1_
USER_LOW_LIMIT/Pmin
ALARM WINDOW if
necessary.
(
See also Operating
Instructions BA00303P,
parameter description or
these Operating Instructions)
55
– Loose connection at sensor
cable.
– Wait a short period of time
and tighten the connection, or
avoid loose connection.
731 Alarm/
Warning
S>Pmax ALARM
WINDOW
(PRESSURE_1_UER_
HIGH_LIMIT) overshot
19
0
– Pressure measured value has
overshot the value specified
for the PRESSURE_1_USER_
HIGH_LIMIT/Pmax ALARM
WINDOW parameter.
– Check system/pressure
measured value.
– Change value for
PRESSURE_1_USER_ HIGH_
LIMIT/Pmax ALARM
WINDOW if necessary.
(
See also Operating
Instructions BA00303P,
parameter description or
these Operating Instructions)
54
732 Alarm/
Warning
S>Tmin ALARM
WINDOW
(TEMPERATURE_1_
USER_LOW_LIMIT)
undershot
19
0
– Temperature measured value
has undershot the value
specified for the
TEMPERATURE_1_USER_
LOW_LIMIT/Tmin ALARM
WINDOW parameter.
– Check system/temperature
measured value.
– Change value for
TEMPERATURE_1_
USER_LOW_LIMIT/Tmin
ALARM WINDOW if
necessary.
(
See also Operating
Instructions BA00303P,
parameter description or
these Operating Instructions)
57
– Loose connection at sensor
cable.
– Wait a short period of time
and tighten the connection, or
avoid loose connection.
Diagnostic
Code
Error
response
Message/description XD_
ERROR
Value Bit
BLOCK_
ERROR
Value Bit
Cause
Measure
Prio-
rity