Commissioning
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
88
Hauser
7.10.4 Transmission of independent event messages on the bus
Event priority
Event messages are only transmitted on the bus if their priority is between 2 and 15. Priority
1 events are displayed but are not transmitted on the bus. Events whose priority is 0 are
ignored. All events are assigned the priority 0 in the factory setting. It is possible to change
the priority individually for the four assignment parameters.
Example
The priority of the "Failure" category is to be set to "2" .
1. In the FieldCare navigation window navigate to
Expert
Field Device Diagnostics
Configuration
2. Select the "Standard area" tab and set the priority to "2" in the "Failure" column (D).
Suppressing certain events
It is possible to suppress certain events during transmission on the bus using a "mask" check
box. While these events are still displayed, they are not transmitted as alert objects on the
bus. This mask check box can be found in FieldCare under
Expert
Field Device Diagnostic
Configuration
. The mask check box acts as a negative check box, i.e. if a field is selected
the associated events are not transmitted on the bus.
(D)