Commissioning
Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
84
Hauser
2. In the
Failure
column search for the
Highest Severity Electronic
group and disable the
associated check box (A). Enable the appropriate check box in the
Function
column (B).
Please note that the "Accept" button must be pressed to confirm each entry.
It must be ensured that the appropriate bit is set in at least one of the assignment
parameters for each event group. Otherwise a category is not transmitted with the event via
the bus. The control system will therefore generally ignore the presence of the event.
The detection of diagnostic events and the transmission of the messages on the bus is
configured on the FieldCare page
Expert
Field Device Diagnostic
Configuration
. The
"Mask" column is used for the transmission of the message on the bus. It must be noted that
device messages can still be transmitted by polling the active bits in Status 1 and 2. The mask
check box acts as a negative check box, i.e. if a field is selected the associated events are not
transmitted on the bus. The Resource Block must be set to the
Auto
mode to transmit status
information on the bus.
(A)
(B)