Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Diagnostics and troubleshooting
Hauser
105
740 Alarm/
warning
M>Calculation
overflow, bad
configuration
20
7
– Level measuring mode: the
measured pressure has
undershot the value for
SCALE_IN, EU_0/HYDR.
PRESS. MIN. or overshot the
value for SCALE_IN,
EU_100/HYDR. PRESS MAX.
– Check configuration and
recalibrate if necessary.
– Select a device with a suitable
measuring range.
29
– Level measuring mode: the
measured level has undershot
the value for LEVEL MIN or
overshot the value for LEVEL
MAX
– Check configuration and
recalibrate the device if
necessary (
see Operating
Instructions BA00303P,
parameter description, LEVEL
MIN. parameter).
– Flow measuring mode: the
measured pressure has
undershot the value for
SCALE_IN, EU_100/MAX.
PRESS FLOW.
– Check configuration and
recalibrate if necessary.
– Select a device with a suitable
measuring range.
745 Warning
M>Sensor
data
unknown
17
0
– Sensor does not suit the
device (electronic sensor
nameplate). Device continues
measuring.
– Replace sensor with a suitable
sensor.
66
Diagnostic
Code
Error
response
Message/description XD_
ERROR
Value Bit
BLOCK_
ERROR
Value Bit
Cause
Measure
Prio-
rity