Deltabar S FMD77, FMD78, PMD75 with FOUNDATION Fieldbus
Operation
Hauser
53
6.4.4
Accepting pressure present at device as value
Example: performing position adjustment.
P01-xxxxxxxx-19-xx-xx-en-030
1. Press "+" or "–" until "0" is displayed.
2. Press the "E" key to confirm "0".
The cursor goes to the next position.
is displayed
and highlighted in black.
See next graphic.
P01-xxxxxxxx-19-xx-xx-en-031
Press "E" to save the new value and exit the editing
mode.
See next graphic.
P01-xxxxxxxx-19-xx-xx-en-032
The new value for the damping is 30.0 s.
– Go to the next parameter with "E" .
– Press "+" or "–" to go back to the editing mode.
Onsite display
Operation
P01-xxxxxxxx-19-xx-xx-en-158
The bottom line on the onsite display displays the
pressure present, 3.9 mbar in this example.
P01-xxxxxxxx-19-xx-xx-en-159
Use "+" or "–" to switch to the "Confirm" option. The
active option is highlighted in black.
P01-xxxxxxxx-19-xx-xx-en-037
Using the "E" key, assign the value (3.9 mbar) to the
POS. ZERO ADJUST parameter. The device confirms the
adjustment and goes back to the parameter, here POS.
ZERO ADJUST (see next graphic).
P01-xxxxxxxx-19-xx-xx-en-160
Go to the next parameter with "E" .
Onsite display
Operation