FAP54 Programming
37
CURRENT INPUT MODULE 4-20 mA (CI)
SMOKE-HEAT (SH)
PULSED INPUT
Test
Type of test
INFO1
INFO2
TST
0
Primary and tertiary
measurement
Primary measurement
(current, expressed in mA)
Tertiary measurement
(temperature)
>0<
1
----
>1<
2
Reading of alarm thresholds
currently used by the device
Alarm threshold 1
(current, expressed in mA)
Alarm threshold 2
(current, expressed in mA)
>2<
3
Red LED switching on
“OK” displayed
>3<
4
Green LED switching on
“OK” displayed
>4<
5
Activation of outputs and
relays
“OK” displayed
>5<
6
Check type of device
Display of device type
>6<
7
----
>7<
8
----
>8<
9
----
>9<
Test
Type of test
INFO1
INFO2
TST
0
Primary and tertiary
measurement
Primary measurement
(smoke level)
Tertiary measurement
(temperature)
>0<
1
Calculation of device dirt
percentage and sensitivity
index of the device
Dirt percentage
Sensitivity index
>1<
2
Sample of alarm threshold
(smoke
threshold
and
temperature threshold)
Display of alarm threshold
(smoke threshold)
Display
of
alarm
threshold
(temperature
threshold)
>2<
3
Red LED switching on
“OK” displayed
>3<
4
Green LED switching on
“OK” displayed
>4<
5
Activation of outputs and
relays
“OK” displayed
>5<
6
Check type of device
Display of device type
>6<
7
Detector adaptation
(to be carried out when test 1
is in progress)
The dirt percentage is still
displayed
The
sensitivity
index
keeps being displayed
>7<
8
Check smoke alarm
“OK” or “FAIL” displayed
Primary measurement
(smoke level)
>8<
9
Check thermal alarm
“OK” or “FAIL” displayed
>9<
Test
Type of test
INFO1
INFO2
TST
0
Primary and tertiary
measurement
Primary measurement
Tertiary measurement
(temperature)
>0<
1
Secondary measurement
Secondary measurement
(input 2)
>1<
2
----
>2<
3
Red LED switching on
“OK” displayed
>3<
4
Green LED switching on
“OK” displayed
>4<
5
Activation of outputs and
relays
“OK” displayed
>5<
6
Check type of device
Display of device type
>6<
7
----
>7<
8
----
>8<
9
----
>9<