FAP54 Programming
117
[1] INSTALLATION DATE
[2] LAST PERIODIC CHECK DATE
[3] CONFORMITY DECLARATION DATE
[4] NUMBER OF CIRCUITS AND DEVICES
[5] PERIODIC CHECK
[6] LIST OF ALARMS PER DATA
[7] LIST OF DETECTORS STATE
[8] DISABLE MAINTENANCE
ACTIVATION MAINTENANCE
CONFIRM?
[1] YES
[2] NO
ACTIVATION MAINTENANCE
PROCEDURE COMPLETED
[OK] CONTINUE
[1] PERIODIC MAINTENANCE
It allows the execution of the periodic maintenance of the devices in the field.
[2] MAINTENANCE NOW
It starts immediately the maintenance operation.
[3] VERIFY BY LEVEL
This procedure finds out the detectors whose average read smoke level is greater (less) than a predefined user level
and, for each one of these detectors, several related information are shown.
[4] VERIFICATION BY ADDRESS
The same information shown in the “VERIFY BY LEVEL” procedure is retrieved and shown for a device whose
coordinates are explicitly specified by the user.
[5] SET TIME/INTERVAL
It allows to set the time and interval for the automatic execution of maintenance.
[6] PASSWORD
This menu temporarily disables the request for entering level 2 passwords.
4.1.1
Periodic Maintenance
The periodic maintenance allows scheduling, management and traceability of maintenance operations performed by
the maintenance technician of the fire detection system.
In order to perform correctly this functionality by the control panel, the system date must be set correctly. Therefore
the following will apply:
Each time the control unit is powered on, a general “date / time check” failure event is generated with the
relative signalling.
The general failure event of "date / time check" becomes clearable (through GENERAL RESET) only after
setting the date in the clock setting menu (if you try to clear it before setting the date, the event is signalled
again).
After entering the advanced level 2 password, the user accesses the following periodic maintenance main menu, if
this feature is enabled:
NOTA:
if the graphic display is present, a bar will appear in the lower part of the display indicating the
percentage of tested devices, and the icon representing maintenance.
If the feature is disabled, the following menu is displayed through which the user can enable it:
By selecting
1
, the feature is enabled and the following confirmation message is displayed:
Pressing
OK
displays the main periodic maintenance menu.