FAP54 Programming
17
MAINT. Z020 C01 P018 SM GD000
KITCHEN SMOKE DETECTOR GZ000
>MN001
SP000
SLAVE 050 HANGAR GD000
MAINT. Z020 C01 P018 SM GZ000
MN000
>SP001
SLAVE 050 HANGAR GD000
ACTIVE EXCLUSIONS 007 GZ000
MN000
>SP001
2.1.5 Maintenance display
The display of a device requiring maintenance allows the immediate recognition of an optical smoke detector which
needs to be replaced or cleaned as it is no longer reliable. Therefore, the display will show the information necessary
to identify the device on the circuit.
2.1.6 Slave control panel display
This paragraph is valid only if the control panel is configured as a MASTER and it is connected to a network of SLAVE
control panels.
Any event occurring on a SLAVE control panel is notified to the MASTER control panel, which shows it by using two
rows, according to the following rules:
the first row shows the address and name of the SLAVE control panel affected by the event,
the second row equals the first row used by the SLAVE control panel to show the event on its own display.
For instance, suppose that the SLAVE control panel with address 50 and named “HANGAR” is affected by a
maintenance event on a detector. This SLAVE control panel, then, shows the following message on its display:
The MASTER control panel to whom the SLAVE control panel is connected shows the following information:
This message says to the user that the smoke detector, located on circuit 1 in the SLAVE 50 and having the address
18, requests a maintenance intervention.
Alarms, faults and maintenance events occurring on a SLAVE control panel are displayed on the MASTER control
panel’s display according to the aforementioned rule (address and name of the SLAVE control panel plus the first row
of the event shown in the SLAVE control panel).
The events of exclusion/inclusion occurring on a SLAVE control panel are handled in a different way:
If a SLAVE control panel is affected by at least one exclusion, the MASTER control panel shows a message like this:
This message indicates the number of elements currently excluded on the SLAVE control panel (in the example, there
are 7 active exclusions on the SLAVE control panel).
If all the currently excluded elements are re-included, the above message is not shown anymore.
MAINT. Z020 C01 P018 SM GD000
KITCHEN DETECTOR GZ000
>MN001
SP000
Device name
Relevant zone
Address of device
Type of device
Circuit of device