FAP54 Programming
ZONE: XXX
NAME: XXXXX
CIRCUIT: XX
ZONE: XXX
NAME: XXXXX
CIRCUIT: XX
OUTPUT MODULES NOT PRESENT
ZONE: XXX
ZONE: 113
NAME: XXXXX
CIRCUIT: 05 ADDR: 012 ID: 01
NAME: XXXXXXXXXX
ZONE: 113
NAME: XXXXX
CIRCUIT: 05 ADDR: 015 ID: --
NAME: XXXXXXXXXX
3.2.3
Associate output module to zone
Type in the number of the zone to be associated with the output modules and then confirm with
OK
.
Now enter the circuit number where the output module to be associated is located and press
OK
.
If the circuit does not have any output module, the following message will be displayed:
Instead, if the circuit has at least one output module, the address of the first output module located on the circuit will
be displayed. If the user presses
OK
, the name of the output module will be shown as well.
If the module already belongs to the zone, the identifier ID takes on a meaningful value (1 - 50), otherwise the field
remains empty.
In the following example, the output module on circuit 5 with address 12 is associated to the zone 113 and it is in the
first position of the list of the max 50 output modules that can be associated to the zone:
In this case, conversely, the output module on circuit 5 with address 15 is not associated to the zone 113:
If an output module is not associated to the zone, press
OK
to proceed with the association. In this case, if the list of
max 50 modules that can be associated to the zone is not full, the coordinates of the module are stored in first free
position of the list and the index to this position is displayed in the ID field.
Press
<
to delete an already present association. In this case, the ID field for the currently displayed output module
will be empty again.
NOTE
:
when the output modules are shared among several zones programmed with different modes, the module
operation, as far as the general alarm function is concerned, will be controlled by the last association performed.