FAP54 Programming
115
PROGRAMMABLE RELAY
AC DETECTION
DELAY: XX
PROGRAMMABLE RELAY
EXCLUSION
PROGRAMMABLE RELAY
[1] # INCLUDED
[2] EXCLUDED
[1] ALARM VERIFICATION TIME
[2] HOTEL RELOAD TIME
ALARM VERIFICATION TIME XX
HOTEL RELOAD TIME XX
VERIFY
This screen view makes it possible to check the relay programming mode (AC/exclusion) and the associated
delay (for the AC DETECTION relay).
Or:
INCLUDE/ESCLUDE
Through this menu it is possible to include/exclude the programmable relay:
3.8.7 Alarm timers
The programming menu for the alarm general timers is the following:
3.8.7.1 Alarm verification timer
When a zone or group is in alarm condition and the siren output activation delay is running, by pressing the
ACK
key
the Alarm Verification timer is added to the residual delay. The increment occurs only the first time
ACK
is pressed.
Further pressure of
ACK
will not affect the residual delay for the zone.
Enter the desired value (range 0
10, expressed in minutes) and confirm with
OK
:
To disable the alarm verification time, set the value on
0
.
When the timing of a group or zone reaches the value 0 and the passage to the new alarm condition occurs with the
siren output active, the intervention on the ACK key no longer involves loading the timer.
3.8.7.2 Hotel reload time
The Hotel Reload timer is used when a zone programmed in HOTEL mode switches to alarm condition. For further
details, please refer to
paragraph 1.9 OPERATING MODES
which describes the operating modes of the zones.
Enter the desired value (range 0÷10, expressed in minutes) and confirm with
OK
:
The maximum loading time is
9
minutes.
When the reload time is set on
0
, at the second device in alarm, the zone will automatically switch to the alarm
condition; when the set value is
10
, the reload time is disabled and the zone timer is not changed.