FAP54 Programming
73
MEMBERSHIP TO MODULE 4I4O
[1] YES
[2] # NO
RESTORE DEFAULT VALUES
[1] YES
[2] # NO
CIRCUIT: XX DEVICE: XXX TYPE: XX
NAME: XXXXX
[1] # INCLUDED
[2] EXCLUDED
TONE A1/A2
[1] OFF
[2] # ON
3.4.3.4 Membership to module
4I4O
This options says whether the output module belongs to a multiple I/O module or not.
Press
1
to say that output module belongs to a multiple I/O module.
Press
2
to say that output module is a single I/O module.
The currently active option is highlighted by the # symbol.
Press
OK
to confirm the choice. Press
ESC
to return to the previous menu.
3.4.3.5 Tone A1/A2
This option, valid in the case of addressed bases and addressed sounders, makes the device activate with a different
acoustic mode depending on the alarm level (1 or 2) of the zone which the device belongs to.
In order to enable dual tone, press key
2
. To disable it, press key
1.
The currently active option is highlighted by the # symbol.
Press
OK
to confirm the choice. Press
ESC
to return to the previous menu.
3.4.3.6 Default
Press
1
to restore the factory setting values.
The currently active option is indicated by # symbol .
The
OK
key must be pressed in order to confirm the configuration. Press
ESC
to return to the previous menu.
Below we can find the factory setting values of the output module:
SILENCE SIREN:
YES
GENERAL ALARM:
NO
ACTIVATION:
ALARM 2 (=>ALARM WITH SIREN OUTPUT ENABLED)
MEMBERSHIP TO MODULE 4I4O:
NO
TYPE:
C
TONE A1/A2:
NO (applicability: bases and addressed plates)
3.4.4 Include/Exclude
The following screen view is displayed which shows the device related information (coordinates, type and name) and
where it is possible to include or exclude it.
The choice is confirmed by pressing
OK
key.
When a device is excluded and then the related zone is excluded and subsequently included, the device is still
excluded.
The exclusion is signalled by the control panel front side LEDs, it is shown on the display and stored in the event log
.
The exclusion also implies the activation of the exclusion relay, if the programmed relay is configured as exclusion
relay.
If a device is included and then excluded or vice versa, the new configuration will be transmitted to the device at the
end of the programming phase, when the system goes back to monitoring.