FAP54 Programming
125
REFERENCE FOR MAINTENANCE: < 70
CIRCUIT: XX DEVICE: XXX TYPE: SM
NAME:XXXXX
MSR:059 ALM:109 REF:059 SI:+000% DI:000%
REFERENCE FOR MAINTENANCE: < 40
DEVICE NOT FOUND
[ESC] BACK
CIRCUIT: XX
CIRCUIT: XX
REFERENCE FOR MAINTENANCE: xx
If the search does not produce any results, the following message will be displayed:
Instead, if some devices are found, the information concerning the first device in the list will be displayed:
To show the previous/next device that meets the search criteria, press keys
and
.
To go back to the previous menus, press
ESC.
For each device whose average read smoke level is greater/less than the threshold set by the user, the following
information is retrieved and shown:
Coordinates (circuit and address)
Type (smoke or smoke/heat)
Name of the device
Average read smoke levels (MSR)
Alarm threshold (ALM)
Reference level (REF)
Sensitivity index (SI)
Dirt index (DI)
During the search of detectors meeting the required conditions, the field monitoring on the selected circuit is not active.
The cumulative level verification, accessed by selecting 2 from the “Verify by level” menu), carries out the level
verification procedure in a cumulative way on ALL smoke detectors in a circuit.
First, enter the circuit where the procedure will be applied, then enter the threshold to be compared with the reference
value of all the detectors of the circuit:
After entering these parameters, the control panel stops scanning the selected circuit and starts reading the current
reference level of each smoke or smoke/heat detector. The reference levels, then, will be compared with the
previously set threshold and the following information will be displayed:
The total number of detectors with optical section available on the circuit
The number of detectors whose reference value > threshold set
The total number of critical detectors (reference value > 120)
The maximum reference value reported by a detector (its address is shown as well)
TOTAL NUMBER OF SMOKE DETECTORS: XXX
NUMBER DETECTORS WITH REF > XXX: XXX
NUMBER OF CRITICAL DETECTORS > XXX: XXX
REF MAX: XXX (ADDR: XXX)