FAP54 Programming
87
RESET TIME: XX
RESET OUTPUT
[1] # RESET OUTPUT DISABLED
[2] RESET OUTPUT ENABLED
RESTORE DEFAULT VALUES
[1] YES
[2] # NO
SINGLE/MULTI THRESHOLD
[1] # SINGLE THRESHOLD
[2] MULTIPLE THRESHOLD
RECOVERY TIME: XX
Press key
4
to configure the working mode, in single or multi threshold, of the module:
Press
1
to set the module operation with single threshold.
Press
2
to set the module operation with multiple threshold.
With
OK
you confirm selection. With
ESC
you go back to the previous menu without changing the current state.
Press key
5
to enable/disable the reset output of the module:
Press
1
to disable the module reset output.
Press
2
to enable the module reset output.
With
OK
you confirm selection. With
ESC
you go back to the previous menu without changing the current state.
Press key
6
to configure the reset time:
Enter the reset time in the range 1
20.
With
OK
you confirm selection. With
ESC
you go back to the previous menu without changing the previous value.
Press key
7
to set the recovery time:
Enter the recovery time in the range 60
255 seconds (default = 60 sec).
With
OK
you confirm selection. With
ESC
you go back to the previous menu without changing the previous value.
Press key
8
to restore the factory settings in the device configuration.
To restore default values press
1
.
The active option is signalled by # symbol.
With
OK
you confirm selection. With
ESC
you go back to the previous menu without changing the current state.
The factory setting values of the parameters of the latched input module are listed below:
REPETITION ACTIVE:
YES
LED ACTIVE:
YES
FREQUENT BLINKING:
YES
THRESHOLD:
SINGLE
RESET TIME:
3
RESET OUTPUT:
ENABLED
RECOVERY TIME:
60
Содержание FAP54
Страница 151: ...FAP54 Programming 151 ...