FAP54 Programming
LED ACTIVE YES /NO
FREQUENT BLINKING YES /NO
FW XXXX-XX
TYPE C YES /NO
RESET TIME X
FW XXXX-XX
LED ACTIVE YES /NO
FREQUENT BLINKING YES/NO
THRESHOLD SINGLE/MULTIPLE
RESET OUTPUT YES /NO
DIP SWITCH 1-2-3: OFF/ON-OFF/ON-OFF/ON
THRESHOLD 1: XX.X (mA)
THRESHOLD 2: XX.X (mA)
LED ACTIVE YES /NO
FREQUENT BLINKING YES /NO
FW XXXX-XX
3.7.1.6 Bathroom call cord (TB)
If the device is a bathroom call cord, the following parameters will be displayed:
LED ACTIVE
: it shows the LED blinking activation as a result of the control panel query.
FREQUENT BLINKING
: if it is set, the green LED will flash every time the device receives a measurement
command.
FW
: it is the device firmware code, revision included.
3.7.1.7 Latched input with siren output (IS)
If the device is a latched input with siren output, the following parameters will be displayed:
LED ACTIVE
: it shows the LED blinking activation as a result of the control panel query.
FREQUENT BLINKING
: if it is set, the green LED will flash every time the device receives a measurement
command.
THRESHOLD
: it shows the single threshold or multi-threshold operating mode of the module.
RESET OUTPUT
: it says whether the reset output in the module is enabled or not
TYPE C
: it indicates whether the module is a type C one or not.
RESET TIME
: it is the time in seconds (1
20 sec.; step 1 sec.) during which the reset output is active.
FW
: it is the device firmware code, revision included.
3.7.1.8 Input module 4-20 mA
If the device is a an input module 4-20 mA, the following parameters will be displayed:
LED ACTIVE
: it shows the LED blinking activation during the control panel query.
FREQUENT BLINKING
: if it is set, the green LED will flash every time the device receives a measurement
command.
FW
: it is the device firmware code, revision included.
DIP SWITCH 1-2-3
: it indicates the current configuration of dip switches in the device.
THRESHOLD 1/2
: it indicates the user defined alarm thresholds 1 and 2. The device uses these thresholds
when the dip switches are configured as OFF-OFF-OFF.