126
FAP54 Programming
CIRCUIT: XX
CIRCUIT: XX
DEVICE: XXX
CIRCUIT: XX
DEVICE: XXX
TYPE: XX
CIRCUIT: XX
DEVICE: XXX TYPE: SM
NAME:XXXXX
MSR:059 ALM:109 REF:059 SI:+000% DI:000%
In the case of control panel with graphic display, the lower part of the display shows three histograms representing, in
graphical form, the information reported in the textual part of the display, i.e.:
The total amount of smoke or smoke/heat detectors of the circuit
The number of smoke or smoke/heat detectors with current reference value > threshold set by the user
The number of smoke or smoke/heat critical detectors
The total area of each histogram shows the maximum capacity of the circuit (128 devices).
4.1.4
Verification by address
This menu makes the control panel retrieve from a smoke or smoke/heat detector whose coordinates are
specified by the user the following information:
Type (smoke – SM or smoke/heat – SH)
Name of the device
Average read smoke levels (MSR)
Alarm threshold (ALM)
Reference level (REF)
Sensitivity index (SI)
Dirt index (DI)
The user is required to insert the number of the circuit:
and then the address of the device:
If the selected device is not a smoke or smoke/heat detector, the actual type of the device is shown for a couple of
seconds:
If the selected device is a smoke or smoke/heat detector, the required information is retrieved from the device and is
shown as follows:
For the meaning of each value shown, please refer to the previous paragraph.
By pressing
ESC
, the user goes back to the insertion of the device address.