FAP54 Programming
11
For the
zones
and
groups of devices
, the following applies:
Single knock
When the control panel is in idle condition and detects one or more devices in alarm, it
switches to the alarm condition with siren output enabled.
Single knock
with delay
When the control panel is idle condition and detects one or more alarm devices, it switches
to the alarm condition with siren output disabled and starts an activation timer. When the
timer expires, the control panel switches to the alarm condition with siren output enabled.
Multiple
knock
For zones programmed in “Fire” operating mode, the following applies:
when the control panel is in idle condition and one alarm from a device belonging to the
zone is detected, the panel switches to the alarm condition with siren output disabled. As
soon as an alarm from another device of the same zone is detected, the panel goes to the
alarm condition with siren output enabled.
For zones programmed in “Technological” operating mode and groups the following
applies:
when the control panel is in idle condition and one or more alarm devices are detected in
the same zone/group and the sum of their weights is less than the weight assigned to the
zone/group, the control panel switches to the alarm condition with siren output disabled;
when the sum of the alarm device weights in the same zone/group is equal to or greater
than the weight assigned to the zone/group, the control panel switches to the alarm
condition with siren output enabled.
Multiple knock
with delay
For zones programmed in “Fire” operating mode, the following applies
:
when the control panel is in idle condition and one alarm from a device belonging to the
zone is detected, the panel switches to the alarm condition with siren output disabled. As
soon as another alarm from a device of the same zone is detected, the panel activates the
timer for the activation of the siren output. When this timer expires, the control panel
switches to the alarm condition with siren output enabled.
NOTE
: if the control panel is in idle condition and a manual call point is pressed, the
control panel switches to the alarm condition with siren output disabled and the activation
timer is started at once.
For zones programmed in “Technological” operating mode and groups the following
applies
:
when the control panel is in idle condition and one or more alarms from devices belonging
to the same zone/group are detected and the sum of their weights is less than the weight of
the zone/group, the control panel switches to the alarm condition with siren output disabled;
when the sum of the alarm device weights in the same zone/group is equal to or greater
than the weight of the zone/group, the control panel starts the timer for the activation of the
siren output. When the timer expires, the control panel switches to the alarm condition with
siren output enabled.
Alarm 1 only
This mode is only applicable to zones/groups programmed with “technological” mode
:
When the control panel is in idle condition and one or more devices detect an alarm, the
control panel switches to the alarm condition with siren output disabled. If further devices
detect an alarm, the control panel keeps being in the state of alarm condition with siren
output disabled.
Multiple knock
with reset
This mode is only applicable to technological zones:
When the control panel is in idle condition and one or more alarm devices are detected in
the same zone and the sum of their weights is less than the weight of the zone, the control
panel switches to the alarm condition with siren output disabled
and starts the reset timer;
when the sum of the alarm device weights in the same zone is equal to or greater than the
weight of the zone, the control panel switches to the alarm condition with siren output
enabled.
When the reset timer expires, the control panel cancels the alarm condition and returns to
idle state.
Hotel
This mode is only applicable to zones programmed in “Fire” operating mode
:
When the control panel detects a device in alarm, it switches to the alarm condition with
siren output disabled and starts the timer associated with the device
Tp
. If another alarm is
detected by another device before the expiration of
Tp
, the remaining amount of
Tp
is
compared to the hotel reload time
Th
. If
Tp > Th
,
Tp
is reloaded with
Th
, otherwise no
reload is done. In any case,
Tp
keeps running and, on its expiration, the control panel
switches to the alarm condition with siren output enabled.