FAP54 Programming
RS232/485 module (optional)
Module to be installed directly to the CPU board in order to enable the communication between:
o
MASTER panel and SLAVE panels
o
FAP panel and the LCD annunciators
o
FAP panel and the printer module
LAN / TCP / IP500 module (optional)
Module which makes it possible to connect the control panel to a LAN. It is installed directly on the CPU board.
This module operates as an E/J type communicator for transmission of alarms and faults to a remote fire alarm
receiving centre.
IT500F Interface (optional)
Interface which makes it possible to connect the control panel to a LAN via Ethernet (wired) or WiFi (radio). This
interface operates as an E/J type communicator for transmission of alarms and faults to the “My Elkron Family”
APP installed on a Smartphone or Tablet.
2.4 EMERGENCY OPERATION
The modular structure of FAP54 allows the complete control of the detection field also if the CPU board is faulty. In
this case, as a result of the smart circuit modules, both the monitoring of the field and the notification of alarms are
ensured through the relays and alarm indicators.
However, it is important to bear in mind that this mode does not replace the normal control panel operation, but it is an
emergency operation
.
It is also necessary to specify that all the zone/group associations of the devices are no longer valid: each module
signals the alarm condition when a detector on its line reveals an alarm condition and the same module activates all
the type "C" actuators present on its lines of revelation.