CPX230NWB ALARM CONTROL PANEL – INSTALLER MANUAL
40 / 144
EN
where:
XX –
determines the number of output from
01
to
03
; entering number
00
will change
the parameters for all outputs in the system,
Y –
number of parameter related to a given output,
Z
- number (or value) of the next parameter;
For Y=0 –
complex function, the initiation of which configures the parameters listed
below as another set of parameters;
Example: Change of many parameters at the time for output 1 using complex function –
output 1 is to be set as alarm signaling with activation time 120 seconds:
For Y=1 –
type of output (DEC type parameter), possible values for the parameter
Z
:
o
0 – not used,
o
1 – signaling alarm,
o
2 – armed status,
o
3 – power failure,
o
4 – ATS failure – no communication with receiving server.
o
5 – GSM signal jamming indicator
o
6 – chirp on arm/disarm
o
7 – chirp on arm/disarm and signaling alarm
Example: Change of 3 output type into triggered by power failure:
For Y=2 –
time of output activation
Z
in seconds (DEC type parameter), ; if 0 is set,
output will operate in bi-stable mode.
Example: Change of a single parameter – operation mode of number 2 output into bi-stable
operation mode:
It is possible to configure the chirp options using following patterns:
For Y=3 –
chirp signal duration
Z
in milliseconds;
Example: change of chirp signal duration of all zones into 600 milliseconds
Note:
In case of complex function (programming many
parameters at the time) after the parameter is entered and confirmed
with
the parameter is saved in the configuration memory and the
system waits for entering another parameter, and so on, until all
parameters of the complex service function are entered. Press
to
cancel changes entered in currently configured parameter only and
exit service function – previously entered parameters, confirmed with
,
will not be cancelled.