CPX230NWB ALARM CONTROL PANEL – INSTALLER MANUAL
113 / 144
EN
8.
GRADE 2 SETTINGS
8.1.
GRADE 2 SETTINGS
To meet the requirements of EN 50131 standard for Grade 2, do the following:
Set the entry time to be no longer than 45 seconds.
The alarm outputs should be configured as follows: operation time of acoustic sirens
should be not shorter than 90 second and no longer than 15 minutes.
Set the zones sensitivity less than 400 ms.
Set interlocking input zones to value from 3 to 10
Set the power loss time to be no longer than 60 minutes (see item 4.3.2. and see
item 6.6.1.3.).
Use user codes with a length of at least 5 characters.
As an emergency power source use 12V lead-acid sealed battery connected to the
control panel. The battery capacity should be sufficient to operate the system
without a power supply for 12 hours.
In the GPRS Transmitters Configurator (see item 6.4.) or in the installer menu (see
item 4.3.4.) set the System Options:
- enable option “Show failures history with SYSTEM diode”
- disable option “Ignore ATS failure”
- enable option “Confirm arming in case of a failure (by pressing #)”
- enable option “Access to alarm and fault memory requires authorization”
- enable option “Alarms and inputs interlocking states are not displayed”
- enable option “Temporary keyboard lock after three access failures”
In the GPRS Transmitters Configurator, in option “Monitoring” (see item 6.6.1.)
enable monitoring of the following events (select the columns: GPRS On, GPRS Off,
SMS On, SMS Off):
- Input A1 – D8
- Input A1 – D8 tamper
- Output 1 – 3 tamper
- Power
- Battery
- Jamming
- Keypad output failure
- Output AUX1 failure
- Output AUX2 failure
- Keypad communication lost
- Keypad tamper
- Keypad power failure
- Clock loss