Chapter 8 Parameters ASDA-M
8-304
Revision December, 2014
Setting Value: 0x45
DI Name
Function Description of Digital Input (DI)
Trigger
Method
Control
Mode
INHP In position mode, when this DI is ON, the external pulse input
command is not working.
(Note: The function has to be set to DI6 so as to ignore the
pulse command)
Level
triggered
PT
Setting Value: 0x46
DI Name
Function Description of Digital Input (DI)
Trigger
Method
Control
Mode
STOP Motor
stops
Rising
edge
triggered
PR
NOTE
1) 11~17 Single control mode; 18~20 Dual control mode.
2) When P2-10
~
P2-17 is set to 0, DI has no function.
Содержание ASD-M-0721 Series
Страница 20: ...ASDA M Chapter 1 Inspection and Model Explanation Revision December 2014 1 7 ASDA M Series Servo Drive top view...
Страница 36: ...ASDA M Chapter 2 Installation Revision December 2014 2 15 Delta Part Number BR1K5W005 3kW 10...
Страница 37: ...Chapter 2 Installation ASDA M 2 16 Revision December 2014 This page is intentionally left blank...
Страница 161: ...Chapter 6 Control Mode of Operation ASDA M 6 36 Revision December 2014 Frequency Domain...
Страница 231: ...Chapter 7 Motion Control ASDA M 7 44 Revision December 2014 This page is intentionally left blank...
Страница 631: ...ASDA M Appendix A Accessories A 10 Revision December 2014 RS 485 Connector Delta Part Number ASD CNIE0B06...
Страница 645: ...Appendix B Maintenance and Inspection ASDA M B 4 Revision December 2014 This page is intentionally left blank...