ASDA-M Chapter 7 Motion Control
Revision December, 2014
7-19
OPT:
OPT selection
7
6
5
4 BIT
-
UNIT
AUTO
INS
※
DI.STP stop and software limit are acceptable.
INS: When this PR is executing, it will interrupt the previous PR.
AUTO: When the speed reaches the constant speed area, the next PR will be loaded
automatically.
UNIT: 0 unit is 0.1r/min; 1 unit is PPS (Pulse Per Second)
ACC/DEC: 0 ~ F, acceleration / deceleration number (4 BIT)
ACC / DEC (4)
Index P5-20 ~ P5-35
SPD: 0 ~ F, target speed number (4 BIT)
SPD (4)
Index P5-60 ~ P5-75
DLY: 0 ~ F, delay time number (4 BIT). The delay after executing this PR. The external INS
is invalid.
DLY (4)
Index P5-40 ~ P5-55
7) PPSITION, Positioning control: (TYPE = 2, PR is completed and stopped), (TYPE = 3,
the next PR is executed automatically after the PR is completed)
31 ~ 28 27 ~ 24 23 ~ 20
19 ~ 16
15 ~ 12
11 ~ 8
7 ~ 4
3 ~ 0 BIT
DW0
-
-
DLY
SPD
DEC
ACC
OPT
2 or 3
DW1
DATA (32 bit): target position, Unit: Pulse of User Unit
OPT:
OPT Selection
7
6
5
4 BIT
Description
CMD
OVLP
IINS
0 0
-
-
Absolute positioning command: Cmd_E=DATA
(Note 1)
1 0
Incremental positioning command: Cmd_E= Cmd_E
+
DATA (Note 2)
0 1
Relative positioning command: Cmd_E= current
feDATA (Note 3)
1 1
CAP positioning command: Cmd_E=CAP position
+DATA (Note 4)
※
DI.STP stop and software limit are acceptable.
INS: When this PR is executing, it will interrupt the previous PR
OVLP: It is allowed to overlap the next PR. When overlapping, please set DLY to 0.
CMD: The calculation of the position terminal command (Cmd_E) is as the followings:
Note 1: Position terminal command is determined by DATA.
Note 2: Position terminal command is determined by the previous terminal command
(Monitor variable 40h) plus DATA.
Note 3: Position terminal command is determined by the current feedback position
Содержание ASD-M-0721 Series
Страница 20: ...ASDA M Chapter 1 Inspection and Model Explanation Revision December 2014 1 7 ASDA M Series Servo Drive top view...
Страница 36: ...ASDA M Chapter 2 Installation Revision December 2014 2 15 Delta Part Number BR1K5W005 3kW 10...
Страница 37: ...Chapter 2 Installation ASDA M 2 16 Revision December 2014 This page is intentionally left blank...
Страница 161: ...Chapter 6 Control Mode of Operation ASDA M 6 36 Revision December 2014 Frequency Domain...
Страница 231: ...Chapter 7 Motion Control ASDA M 7 44 Revision December 2014 This page is intentionally left blank...
Страница 631: ...ASDA M Appendix A Accessories A 10 Revision December 2014 RS 485 Connector Delta Part Number ASD CNIE0B06...
Страница 645: ...Appendix B Maintenance and Inspection ASDA M B 4 Revision December 2014 This page is intentionally left blank...