SiBE18-821_C
Service Check Function
Troubleshooting
345
2.2.2 BRC1D528
If operation stops due to malfunction, the operation lamp on the remote controller blinks, and
error code is displayed. (Even if stop operation is carried out, malfunction contents are
displayed when inspection mode is entered.) The error code enables you to tell what kind of
malfunction caused operation to stop.
Refer to page 350, 351 for error code and malfunction contents.
Note:
1. When you press the [Inspection / Test] button, the inspection display blinks.
2. While in the inspection mode, press the [ON/OFF] button for 5 seconds or more to clear the
failure history indication. In this case, the error code blinks twice and then changes to “
00
” (=
Normal), the UNIT No. changes to “
0
”, and the operation mode automatically switches from
the inspection mode to the normal mode (displaying the set temperature).
Operation lamp
[ON/OFF] button
(R12854)
Inspection display
Display of indoor unit
for which a malfunction
has been detected
[Inspection / Test] button
Error code