SiBE18-821_C
Troubleshooting for Outdoor Unit
Troubleshooting
393
7.8
Refrigerant Overcharged
Remote
Controller
Display
F6
Method of
Malfunction
Detection
Excessive charging of refrigerant is detected during check operation by using outdoor
temperature, outdoor heat exchanger temperature, and liquid pipe temperature.
Malfunction
Decision
Conditions
When the amount of refrigerant, which is calculated during check operation by using outdoor
temperature, outdoor heat exchanger temperature, and liquid pipe temperature, exceeds the
standard.
Supposed
Causes
Refrigerant overcharge
Incorrect installation of outdoor temperature thermistor, outdoor heat exchanger thermistor,
liquid pipe thermistor
Defective outdoor temperature thermistor, outdoor heat exchanger thermistor, liquid pipe
thermistor
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table 2 on page 427.
Remove the outdoor
temperature thermistor,
outdoor heat exchanger
thermistor, liquid pipe
thermistor from the outdoor
PCB and measure the
resistance with a tester.
Check the mounting condition
of the outdoor temperature
thermistor, outdoor heat
exchanger thermistor, liquid
pipe thermistor.
Are the thermistors
installed on pipes
correctly?
Is the
characteristic of the
thermistors normal?
Correct the amount of
refrigerant.
(R13024)
Install the thermistor
correctly.
NO
Replace the defective
thermistor.
NO
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...