Troubleshooting for SA Indoor Unit
SiBE18-821_C
372
Troubleshooting
5.9
Remote Controller Thermistor Abnormality
Remote
Controller
Display
CJ
Method of
Malfunction
Detection
Even if remote controller thermistor is faulty, system is possible to operate by system thermistor.
Malfunction detection is carried out by the temperature detected by remote controller thermistor.
Malfunction
Decision
Conditions
When the remote controller thermistor becomes disconnected or shorted while the unit is
running.
Supposed
Causes
Defective thermistor
Broken wire
Troubleshooting
Note:
To delete the record of error codes, press the ON / OFF button for 4 seconds or more while the
error code is displayed in the inspection mode.
Replace the remote
controller.
External factor other
than equipment
malfunction.
(for example, noise
etc.)
YES
NO
(R13007)
Is "
CJ
"
displayed on the
remote controller
again?
Delete the record of error
codes. (See note.)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...