Outdoor Unit
SiBE18-821_C
446
Removal Procedure
1.5
Removal of Electronic Expansion Valves / Peripheral
Equipments
Procedure
Warning
Be sure to commence the disassembling work after 10 minutes or
more elapsed from all power supplies have been turned off.
Step
Procedure
Points
1
Pull out the 2 electronic
expansion valve coils.
2
Remove the 2 pressure
sensors.
When removing the pressure
sensor, be sure to use 2
wrench as the left figure
shows.
The pressure sensor is
equipped with a gauge port
with check valve. Therefore,
when loosening the nut,
refrigerant leak stops.
(R12996)
Electronic
expansion
valve coil
(main)
(Y1E)
Electronic
expansion
valve coil
(subcooling)
(Y3E)
(R9252)
(R12976)
High pressure sensor (S1NPH)
(R12977)
Low pressure sensor (S1NPL)
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...