SiBE18-821_C
Basic Control
Function
79
2.2
Compressor PI Control
The PI control of compressor capacity is carried out to maintain Te at constant during cooling
operation and Tc at constant during heating operation to ensure stable unit performance.
[Cooling operation]
[Heating operation]
∗
Compressors may operate in a pattern other than those listed in above tables subject to the
operating conditions. Selection of full load operation to/from unload operation is made with
the unload circuit solenoid valve (Y3S). The full load operation is performed with the Y3S set
to OFF, while the unload operation is performed with the Y3S set to ON.
Controls compressor capacity to adjust Te to
achieve target value (TeS).
Te : Low pressure equivalent saturation temperature
(°C)
Te setting (Set in Set-up mode 2)
TeS : Target Te value
(Varies depending on Te setting, operating
frequency, etc.)
L
M (Normal)
(factory
setting)
H
3
6
9
Controls compressor capacity to adjust Tc to
achieve target value (TcS).
Tc : High pressure equivalent saturation temperature
(°C)
Tc setting
TcS : Target Tc value
(Varies depending on Tc setting, operating
frequency, etc.)
L
M (Normal)
(factory
setting)
H
43
46
49
Step
Full-load
Unload
Step
Full-load
Unload
1
36.0 Hz
16
110.0 Hz
2
39.0 Hz
17
116.0 Hz
3
43.0 Hz
18
122.0 Hz
4
47.0 Hz
19
128.0 Hz
5
52.0 Hz
20
134.0 Hz
6
52.0 Hz
57.0 Hz
21
140.0 Hz
7
57.0 Hz
64.0 Hz
22
146.0 Hz
8
62.0 Hz
71.0 Hz
23
152.0 Hz
9
68.0 Hz
78.0 Hz
24
158.0 Hz
10
74.0 Hz
25
164.0 Hz
11
80.0 Hz
26
170.0 Hz
12
86.0 Hz
27
175.0 Hz
13
92.0 Hz
28
180.0 Hz
14
98.0 Hz
29
185.0 Hz
15
104.0 Hz
30
190.0 Hz
31
195.0 Hz
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...