Troubleshooting for BP Unit
Troubleshooting
381
6.5
Transmission Error between Outdoor Unit and BP Unit
Outdoor Unit
Indication
UJ
Method of
Malfunction
Detection
Transmission error is detected when the outdoor unit could not received the data from BP unit
correctly.
Malfunction
Decision
Conditions
When the data from BP unit could not be correctly received continuously for 10 minutes
Supposed
Causes
Incorrect connection of transmission wire
Faulty outdoor unit power supply
Defective BP unit PCB
Defective outdoor unit PCB
Distortion of power supply waveform
Troubleshooting
Check No.14
Refer to P.382
YES
NO
YES
Check No. 14
Check the power supply
waveform.
NO
YES
(R13015)
NO
YES
Check the transmission wire
and the connection orders.
Could be external factor other
than errors.
Probe where the noise comes
from, and apply remedy
required.
Replace the main PCB (A1P)
of the outdoor unit.
Probe the causes for
deformation of power supply
waveform and apply remedy
required.
Is it deformed?
Turn the power supply back
on.
Is it normal?
Is "
UJ
" displayed again?
NO
Replace the main PCB (A1P)
of the outdoor unit.
Is HAP on the
outdoor unit PCB
blinking?
Turn the power supply off.
Check the transmission wire
between outdoor unit - BP
unit
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...