SiBE18-821_C
Field Settings
Test Operation and Field Settings
161
2.3.2 Overview of the Field Settings
: factory set
Note:
1. Any function that is not available on the indoor unit is not displayed.
2.
Mode
No.
First
Code
No.
Description of setting
Second Code No.
01
02
03
04
10
(20)
0
Filter cleaning
sign interval
Ultra
longlife
filter
Li
ght
Approx.
10,000
hrs.
He
a
v
y
Approx.
5,000
hrs.
—
—
Longlife
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
1
Long-life filter type
Longlife
filter
Ultra
longlife filter
—
—
2
Remote controller thermistor
Enabled
Disabled
—
—
3
Filter cleaning sign
Display
No display
—
—
11
(21)
0
Indoor unit number of
simultaneous operation
system
Pair
Twin
Triple
Double twin
1
Simultaneous operation
system individual setting
Unified
setting
Individual
setting
—
—
7
External static pressure
setting
Airflow
adjustment
is OFF
Completion
of airflow
adjustment
Start of
airflow
adjustment
—
12
(22)
1
Forced ON/OFF function
Forced
OFF
ON/OFF
operation
—
—
2
Thermostat differential
changeover (setting for when
using remote sensor)
1°C
0.5°C
—
—
13
(23)
0
High air outlet velocity (for
high ceiling applications)
≤
2.7 m
2.7 ~ 3.0 m
3.0 ~ 3.5 m
—
1
Selection of airflow direction
(setting for when a blocking
pad kit has been installed)
4-way flow
3-way flow
2-way flow
—
3
Selection of airflow function
(setting for when using a
decoration panel for outlet)
Equipped
Not equipped
—
—
4
Airflow direction range setting
Upper
Normal
Lower
—
6
External static pressure
Refer to Note 2.
15
(25)
3
Drain pump operation with
humidifying
Not equipped
Equipped
—
—
: factory set
External static pressure (Pa)
Mode
No.
First
code No.
Second
code No.
FBQ
35 class 50 class 60 class
13 (23)
6
03
30
30
30
04
35
35
40
05
40
40
50
06
45
45
60
07
50
50
70
08
60
60
80
09
70
70
90
10
80
80
100
11
90
90
—
12
100
100
—
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...