Troubleshooting for SA Indoor Unit
Troubleshooting
367
5.4
Swing Motor Lock (FHQ Series)
Remote
Controller
Display
A7
Method of
Malfunction
Detection
The error is detected by the limit switch when the motor turns.
Malfunction
Decision
Conditions
When the ON/OFF micro-switch for position detection cannot be reversed even though the
swing motor is energized for a specified amount of time (about 30 seconds).
Supposed
Causes
Defective swing motor
Defective micro-switch
Disconnection of connector
Defective indoor unit PCB
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connect them correctly.
Replace the indoor unit
PCB.
Replace the swing
motor.
(R12863)
NO
Replace the indoor unit
PCB.
YES
YES
NO
Connect it correctly.
NO
YES
Does the swing motor
swing?
Are the
connectors
correctly connected to X29A
and X14A on the
PCB?
Is the relay
connector of the limit
switch correctly
connected?
YES
YES
Turn the power supply off once
and back on. Check whether the
swing motor swings when the
power supply is turned back on.
Turn the power supply off once
and back on. Measure the output
voltage of connector X29A when
the power supply is turned back
on.
Disconnect X14A, turn the power
supply off once and back on.
Check if the limit switch has
continuity when the power supply
is turned back on.
NO
NO
220-240 VAC?
Does continuity/
no continuity reverse?
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...