![Daikin Super Multi Plus E-Series FTXG25EV1BW Скачать руководство пользователя страница 100](http://html1.mh-extra.com/html/daikin/super-multi-plus-e-series-ftxg25ev1bw/super-multi-plus-e-series-ftxg25ev1bw_service-manual_4705813100.webp)
Protection Control
SiBE18-821_C
88
Function
4. Protection Control
4.1
High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
[In cooling operation]
[In heating operation]
Pc > 3.47 MPa
After 10 sec.
Pc > 3.47 MPa
Pc < 3.23 MPa
Pc > 3.64 MPa
Keeping the current step
After 15 sec.
High pressure not limited
High pressure limited
Pc: High pressure sensor detection value
When occurring 10 times within 60 minutes,
high pressure switch is activated without
high pressure standby, thus outputting the
error code "
E3
".
Upper limit frequency = Max
(R12926)
Upper limit frequency:
3-step down from current
compressor frequency
Upper limit frequency:
1-step up from current
compressor frequency
High pressure
standby
High pressure drop
Pc > 3.04 MPa
After 10 sec.
Pc > 3.04 MPa
Pc < 2.94 MPa
Pc > 3.64 MPa
Keeping the current step
After 60 sec.
High pressure not limited
High pressure limited
Pc: High pressure sensor detection value
When occurring 10 times within 60 minutes,
high pressure switch is activated without
high pressure standby, thus outputting the
error code "
E3
".
Pc < 2.89 MPa
(R12927)
Upper limit frequency:
1-step down from current
compressor frequency
Upper limit frequency:
1-step up from current
compressor frequency
High pressure
standby
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...