Field Settings
SiBE18-821_C
164
Test Operation and Field Settings
Wireless Remote
Controller
(Factory Set is
“1”)
1. Hold down the “
” button and the “
” button at the same time for at least
4 seconds to enter the field setting mode. (“SETTING” is indicated on the display).
2. Press the “
” button and select “A” or “b”. Each time the button is pressed, the
display switches between “A” and “b”.
3. Press the “
” button and “
” button to set the address.
Address can be set from 1 ~ 6, but set it to 1 ~ 3 and to same address as the receiver. (The
receiver does not work with address 4 ~ 6.)
4. Press the “
” button to confirm the setting.
5. Hold down the “
” button for at least 1 second to exit the field setting mode and
return to the normal display.
Multiple Settings
A/b
When the indoor is controlled by outside controller (central remote controller, etc.), it sometimes
does not respond to ON/OFF command or temperature setting command from the remote
controller. Check what setting the customer needs and make the multiple setting as shown
below.
TEST
FAN
up
DOWN
RESERVE
TEST
Field setting mode
Address
Multiple setting
(R12959)
Remote Controller
Indoor Unit
Multiple Setting
Remote Controller
Display
Controlled by other air
conditioners or devices
Other condition
A: Standard
All items are displayed. ON/OFF command and
temperature setting
command cannot be
accepted. (1 long beep
or 3 short beeps
emitted)
b: Multiple display
Operations set only is
displayed shortly after
execution.
All the commands can be accepted (2 short
beeps)
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...