Troubleshooting for RA Indoor Unit
SiBE18-821_C
360
Troubleshooting
4.6
Check for RA Indoor Unit
4.6.1 Fan Motor Connector Output Check
Check No.01
1. Check the connection of connector.
2. Check motor power supply voltage output (pins 4 - 7).
3. Check motor control voltage (pins 4 - 3).
4. Check rotation command voltage output (pins 4 - 2).
5. Check rotation pulse input (pins 4 - 1).
7
6
5
4
3
2
1
Motor power supply voltage (310 ~ 340 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (1~ 5 VDC)
Rotation pulse input
S1
(R12404)