SiBE18-821_C
Indoor Unit Control (RA Models)
Function
101
7.2
Operation Starting Control
Wall Mounted Type E-Series, J-Series
The system carries out the following control at the beginning to conduct every functional parts
properly.
1. Opening the front panel fully
2. Output of the
∆
D signal after the front panel starts moving
3. Opening the flap fully after the front panel opens fully
4. Making the fan rotate when the flap passes over the fan-banned area
Fan-banned area: The fan is prohibited to rotate until the flap angle exceeds certain level.
Control Flow
Timing Chart
(1) Opening the front panel fully
Start
Running
(2) Output of the
∆
D signal after
the front panel starts moving
(4) Making the fan rotate when
the flap passes over the
fan-banned area
(3) Opening the flap fully
(R14072)
Fully close
OFF
Start
ON
Flap
Under running control
Under operation mode control
Under operation mode control
Fan
∆
D
Fully open
Fully open
Fully close
ON
OFF
OFF
Output
ON
∆
0
Fan-banned area
(R11910)
Front
panel
Force supply
(from the
outdoor unit)
The outdoor unit provides force
when it receives the
∆
D signal.
Operation
starting control
: Actual position
of panel or flap
: Additional
control of motor
Содержание Super Multi Plus E-Series FTXG25EV1BW
Страница 1: ...Service Manual E Series SiBE18 821_C Applied Models Super Multi Plus Heat Pump...
Страница 13: ...SiBE18 821_C List of Functions 1 Part 1 List of Functions 1 Functions 2...
Страница 264: ...SA Indoor Unit FFQ FCQ FDBQ FBQ FHQ Series SiBE18 821_C 252 Operation Manual 2 Start 5s 5s 5s 5s 5s End...
Страница 471: ...SiBE18 821_C BP Unit Removal Procedure 459 Step Procedure Points Clamps Q0529...
Страница 491: ...Revision History Date News No Contents 2010 11 9 M 10013 Correction of troubleshooting flowchart AF for SkyAir models...