Part 2. Troubleshooting
2. Error code based troubleshooting
Page 30
13/05/15
|
Version 2.0
Ground source heat pump
2.30. “L5” – Output overcurrent detection
2.31. “L8” – Electronic thermal overload
2.32. “L9” – Stall prevention (time lag)
Trigger
Effect
Reset
Inverter PCB detects overcurrent to power
transistor.
Unit will stop operating.
Via user interface.
Possible cause
Check
Corrective action
Refrigerant circuit is clogged.
Check for possible blockage (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve)).
Power supply is not OK (voltage drop).
Check power supply for voltage dips.
Faulty compressor.
Check compressor (see
).
Replace compressor (see
).
Faulty inverter PCB A10P.
Check inverter PCB (see
Replace inverter PCB (see
Trigger
Effect
Reset
When compressor overload (except dur-
ing startup) is detected.
Unit will stop operating.
Via user interface.
Possible cause
Check
Corrective action
Refrigerant circuit is clogged.
Check for possible blockage (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve)).
Refrigerant overcharge.
Check for refrigerant overcharge.
Charge the system with 1.8 kg refrigerant.
Faulty compressor.
Check compressor (see
).
Replace compressor (see
).
Faulty inverter PCB A10P.
Check inverter PCB (see
Replace inverter PCB (see
Trigger
Effect
Reset
Inverter PCB detects compressor over-
load at start up.
Unit will stop operating.
Via user interface.
Possible cause
Check
Corrective action
Refrigerant circuit is clogged.
Check for possible blockage (blockages
can be checked by measuring the refriger-
ant/pipe temperature. Sudden drop in
temperature could indicate a blockage
(remark: this is not valid for the expansion
valve)).
Refrigerant condition is not OK (HP - LP
> 0,2 MPa at start up).
Check refrigerant condition.
Faulty compressor.
Check compressor (see
).
Replace compressor (see
).
Faulty inverter PCB A10P.
Check inverter PCB (see
Replace inverter PCB (see