ESIE13-03
|
Part 2. Troubleshooting
4. Component checklist
13/05/15
|
Version 2.0
Page 73
Ground source heat pump
4. Slide the magnet (tool part N° 9950038) and gently rotate the magnet to manually operate the expansion valve K1E clockwise
(closing) and counterclockwise (opening).
5. If it is not possible to open the expansion valve K1E with the magnet, the expansion valve K1E is blocked and the expansion
valve K1E body must be replaced, refer to
"Replacing the electronic expansion valve K1E body" on page 133
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the switch box cover, refer to
"Removing the switch box cover" on page 89
.
3. Disconnect the connector X21A from PCB A9P.
4. Measure the 4 electromagnet windings X21: red - white, red orange, red - yellow and red - blue. All windings must read
45 Ohm.
5. If one or more winding measurements fail, replace the expansion valve K1E electromagnet, refer to
expansion valve K1E electromagnet" on page 135
4.14. Thermal protector backup heater Q1L
Electrical check
Technical specification
Description
The thermal protector backup heater Q1L is triggered if the temperature
exceeds 92°C. The thermal protector backup heater Q1L will cut power supply
to the backup heater to prevent the water circuit from overheating.
The thermal protector backup heater Q1L is a
safety component that protects the water circuit
against overtemperature.
Location
Wiring diagram
Switch box
Unit
Check procedure
1
2
3
4
M
Yellow
Blue
Orange
Red
(COM)
White