ESIE13-03
|
Part 4. Maintenance
2. Maintenance procedures
13/05/15
|
Version 2.0
Page 151
Ground source heat pump
2.5. Checking the relief valve of the Domestic Hot Water tank - field supply
2.6. Checking the filters of Space Heating and brine circuit
Actions
Remarks
Open the valve and check the correct operation:
• If the fluid flow is high, no blockage is suspected.
• If the fluid flow is low or contains debris or dirt:
• Open the valve until fluid is without dirt.
• Flush and clean the tank and piping between relief valve
and cold water inlet.
Make sure that all taps and air vent are open, otherwise the tank
might be sucked vacuum and the water will not move.
W
ARNING
Discharged fluid may be very hot!
Actions
Remarks
Follow the actions in below picture:
• The filters are located on top of the unit.
• They are horizontally installed, so there is a possibility that
some fluid comes out when removing the filter cartridges. Use
a small container to collect the fluids.
• Handle the filter with care. Do NOT use excessive force when
you reinsert the filter so as NOT to damage the water filter
mesh.
• Make sure the snap ring is correctly located or leakage might
occur.
Refer to
"Cleaning the brine filter" on page 98
and