ESIE13-03
|
Part 2. Troubleshooting
2. Error code based troubleshooting
13/05/15
|
Version 2.0
Page 33
Ground source heat pump
2.39. “U2” – Power supply voltage abnormality
2.40. “U3-00” – Abnormal stop of underfloor heating dry-out scheduled
operation
2.41. “U4” – Defective indoor-outdoor transmission
Trigger
Effect
Reset
Inverter PCB detects an abnormal power
supply (drop or peak).
Unit will stop operating.
Via user interface.
Possible cause
Check
Corrective action
Power supply is not OK -> imbalance
> 10% (rated power supply: 400 V).
Check power supply for voltage fluctua-
tions (> 10%).
Voltage fluctuations should be less than
10%.
Power supply is not OK -> reverse phase.
Check power supply.
Change two phases with each other.
Faulty inverter PCB A10P.
Check inverter PCB A10P (see
).
Replace inverter PCB A10P (see
Trigger
Effect
Reset
Screed dry-out program was interrupted.
Unit will stop UFH dry-out schedule.
Via user interface -> only possible in
"installer" level.
No heat source detected.
Check backup heater.
Restart screeds dry out program. Refer to
the Installer Reference Guide.
Possible cause
Check
Corrective action
User interface has been turned off.
Check user interface.
Restart screed dry out program. Refer to
the Installer Reference Guide.
Power failure.
Check power supply.
Restart screed dry out program. Refer to
the Installer Reference Guide.
Trigger
Effect
Reset
Hydro PCB detects abnormal transmis-
sion to refrigerant/brine PCB for a certain
time.
Unit will stop operation.
Auto-reset.
Possible cause
Check
Corrective action
Power supply is not OK -> imbalance
> 10% (rated power supply: 400 V).
Check power supply for voltage fluctua-
tions (> 10%).
Voltage fluctuations should be less than
10%.
Wiring between refrigerant/brine PCB
A9P and hydro PCB A1P is not OK.
Check the wiring (refer to the wiring dia-
gram).
Correct the wiring.
Faulty refrigerant/brine PCB A9P.
Replace PCB A9P (see
Faulty hydro PCB A1P.
Replace PCB A1P (see
External factor (e.g. electrical noise)
(cause when error is reset after power
reset, and error happens again after
awhile).
Check for source which could cause elec-
trical interference.