ESIE13-03
|
Part 2. Troubleshooting
2. Error code based troubleshooting
13/05/15
|
Version 2.0
Page 27
Ground source heat pump
2.19. “H9” – Outdoor air thermistor (R1T) abnormality
2.20. “J1” – High pressure sensor abnormality
2.21. “J3” – Discharge thermistor abnormality
2.22. “J5” – Suction thermistor (R3T) abnormality
Trigger
Effect
Reset
Thermistor detects an abnormal value
(open or short circuit).
Unit stops operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty outdoor air thermistor R1T / refrig-
erant/brine PCB A9P.
Check thermistor R1T (see
).
(Remark: also check the LC filter connec-
tion between the X5M terminal and the
PCB A9P.)
Replace thermistor R1T (see
PCB A9P (see
).
Trigger
Effect
Reset
High pressure sensor detects an abnor-
mal value for 3 minutes (> 4,5 MPa or <
-0,05 MPa).
Unit stops operating.
Auto-reset.
Possible cause
Check
Corrective action
Faulty high pressure sensor / refriger-
ant/brine PCB A9P.
Check high pressure sensor (see
Replace the high pressure sensor (see
) or PCB A9P (see
).
Trigger
Effect
Reset
Discharge thermistor detects an abnormal
value (open or short circuit).
Unit stops operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty discharge thermistor (R2T) / refrig-
erant/brine PCB A9P.
Check thermistor R2T (see
).
Replace thermistor R2T (see
PCB A9P (see
).
Trigger
Effect
Reset
Suction thermistor detects an abnormal
value (open or short circuit).
Unit stops operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty suction thermistor (R3T) / refriger-
ant/brine PCB A9P.
Check thermistor R3T (see
).
Replace thermistor R3T (see
PCB A9P (see
).
Содержание EGSQH10S18AA9W