ESIE13-03
|
Part 2. Troubleshooting
4. Component checklist
Page 72
13/05/15
|
Version 2.0
Ground source heat pump
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the switch box cover, refer to the Daikin Altherma ground source heat pump Installer reference guide
(EGSQH10S18AA9W).
3. Disconnect the connector X111A from PCB A10P.
4. Recover the refrigerant.
5. Pressurize the refrigerant circuit at 41.7 bar with nitrogen.
6. Measure the switch contacts between X111A: pin 1 and 2; the switch must be open.
7. Replace the high pressure switch S1PH if the contact is not open, refer to
"Replacing the refrigerant high pressure switch" on
8. Lower the refrigerant circuit pressure to 30 bar.
9. Measure the switch contacts between X111A: pin 1 and 2; the switch must be closed.
10. Replace the high pressure switch S1PH if the contact is not closed, refer to
"Replacing the refrigerant high pressure switch"
4.13. Electronic expansion valve K1E
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Open the Sound Insulation (Front Side Only), refer to
"Opening the sound insulation of the heat pump module (front side only)"
.
3. Remove the electromagnet from the expansion valve K1E.
Electrical check
Technical specification
Description
The expansion valve K1E has a hermetically sealed body with a slide-on step-
ping motor drive coil (480 pulses from fully closed to fully open position).
The expansion valve K1E.
Location
Piping diagram
Switch box
Unit
Check procedure
Blockage check
sensor
switch