Part 2. Troubleshooting
3. Symptom based troubleshooting
13/05/15
|
Version 2.0
Page 51
Ground source heat pump
Compressor (M1C) frequency
limited - suction pipe super-
heat protection function active.
This protection control acti-
vates when suction superheat
is > 10°C and expansion valve
is fully open (480 pulse). Unit
returns to normal operation
when suction superheat is <
4°C.
Remark: check the suction
superheat by measuring the
suction temperature (with con-
tact thermometer) before the
compressor and comparing
with the saturated evaporation
temperature.
Activation of the protection
function can be caused by var-
ious reasons, therefore we
recommend to check the fol-
lowing:
• Check refrigerant charge
• Check expansion valve for
correct operation (see
) and check
suction sensor (R3T) (see
).
• Check
the
refrigerant
circuit for blockages.
Based on the diagnosis exe-
cute one of the following
actions:
• Correct
the
refrigerant
charge (total charge:
1.8 kg)
• Replace
expansion
valve(see
electronic expansion valve
K1E body" on page 133
"Replacing the electronic
expansion valve K1E
electromagnet" on
page 135
) or suction
sensor (R3T)
• Remove
detected
blockages from the
refrigerant circuit
Root cause category: installation
PHE condensor (water side)
(partial) blockage.
Dirty water (particles).
• Check waterflow rate
registered by flowsensor.
• Check water side plate
type heat exchanger for
blockage (see
).
• If required replace the
water plate type heat
exchanger.
• Check the water quality.
Root cause category: component - mechanical
Limited heat exchange
between refrigerant loop and
heat sink inverter could result
in high inverter temperatures
and limited compressor fre-
quency.
• Bad
contact
between
refrigerant loop and
inverter heat sink.
• Lack
of
refrigerant.
Check contact between refrig-
erant loop and inverter PCB
heat sink.
Root cause category: component - electrical
Discharge thermistor (R2T -
A9P) - higher temperature
measured than actual.
Deviation of thermistor (higher
temperature measured than
actual).
Check discharge thermistor
R2T (see
).
Replace discharge thermistor
R2T (see
)or PCB
A9P (see
).
Heat sink inverter thermistor
(R10T - A10P) - deviation.
Deviation of thermistor (higher
temperature measured than
actual).
Check thermistor R10T (see
).
or PCB A10P (see
).
Expansion valve (K1E) incor-
rect control - superheat too
high.
• Faulty suction R3T
thermistor.
• Faulty low pressure liquid
(R4T - A9P) thermistor.
• Faulty expansion valve
control.
• Check
thermistor
R3T
(see
).
•
Check the expansion valve
(see
Replace thermistor R3T (see
) or replace expan-
sion valve(see
Possible failures
Root cause
Check
Corrective action