ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
Page 132
13/05/15
|
Version 2.0
Ground source heat pump
4. Through the opening in the rear of the switch box (6), cut the tie wrap (5).
5. Through the opening in the rear of the switch box, move the manometer capillary (3) towards the top of the Daikin Altherma
GSHP, while pressing the insulation where the manometer capillary (3) is attached with a tie wrap (4) to allow the capillary nut
to pass.
6. Guide the manometer capillary (3) through the opening in the brine manometer support (7).
Figure 52 - Replacing the brine manometer
I
NFORMATION
The manometer capillary (3) is held in position by 2 tie wraps (4, 5); one tie wrap (5) will be cut. Press the insulation at
the position of the tie wrap (4) to release the capillary; the same tie wrap (4) will be used when installing the new water
manometer.
1. Brine manometer
5. Tie wrap
2. Nut (water manometer capillary)
6. Switch box opening
3. Manometer capillary
7. Brine manometer support
4. Tie wrap
7
1
3
4
5
6
2