ESIE13-03
|
Part 3. Repair
2. Unit specific repair procedures
13/05/15
|
Version 2.0
Page 119
Ground source heat pump
Figure 36 - Replacing the water pump - 4
Installation
Figure 37 - Water pump wire strain relief
1. Proceed in reverse order.
2. Fill the water circuit, refer to “To fill the space heating circuit” in the Daikin Altherma ground source heat pump Installer
reference guide.
3. Purge the water circuit, refer to “9.3 Air purge function on the space heating circuit” in the Daikin Altherma ground source heat
pump Installer reference guide.
2.2.13. Replacing the compressor
2.2.13.1 Preliminary actions
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Open the front sound insulation, refer to
"Opening the sound insulation of the heat pump module (front side only)" on page 89
.
3. Remove the (lower) rear panel, refer to
"Removing the lower rear panel" on page 92
.
4. Recover the refrigerant, refer to
"Refrigerant Handling" on page 86
.
5. Place the water expansion vessel next to the Daikin Altherma GSHP, refer to
"Replacing the water expansion vessel" on
.
6. Place the brine expansion vessel next to the Daikin Altherma GSHP, refer to
"Replacing the brine expansion vessel" on
.
1. Nut
3. Water pump
2. Seal
C
AUTION
When installing the water pump wire (2), twist the water pump wires (2) around the frame beam (1) behind the switch
box to ensure strain relief.
1. Frame beam
2. Water pump wire
1
3
1
2
1
2
Содержание EGSQH10S18AA9W
Страница 1: ...Service Manual Ground source heat pump EGSQH10S18AA9W ESIE13 03 Version 2 0 ...
Страница 82: ...ESIE13 03 Part 2 Troubleshooting 4 Component checklist Page 82 13 05 15 Version 2 0 Ground source heat pump ...
Страница 148: ...ESIE13 03 Part 3 Repair 2 Unit specific repair procedures Page 148 13 05 15 Version 2 0 Ground source heat pump ...